WEEK 06 Stage 1 · Concepts 9 hours
Energy, FDD and Re-Tuning
DELIVERABLE Trend-review checklist
Week progress0%
Learning objectives
- >Explain the building re-tuning process
- >Recognize common faults in AHU and plant trends
- >Explain low delta-T syndrome and its effect on pumping
- >Describe what fault detection and diagnostics (FDD) needs in order to work
Sessions
Three 2-hour weeknight sessions plus a weekend block. Check each one off as you finish it.
Quiz
Score: 0 / 5 · aim for 4+
Answer in your notebook first, then reveal the answer and grade yourself honestly.
-
Q1What is building re-tuning?
[ reveal answer ]
A low- or no-cost, systematic review of BAS trends and operations to find and fix operational problems. -
Q2What would simultaneous heating and cooling look like in AHU trends?
[ reveal answer ]
Heating and cooling valves open at the same time, or reheat running while supply air is colder than necessary. -
Q3Pumps sit at minimum speed while loop DP stays well above setpoint. What are two likely causes?
[ reveal answer ]
An oversized pump or a minimum speed set too high, an open bypass, or very low load. -
Q4What is low delta-T syndrome, and how does it affect pumps and chillers?
[ reveal answer ]
The return-minus-supply temperature difference runs below design. That forces more flow, raises pumping energy, and keeps chillers from fully loading. -
Q5According to the Guideline 36 AFDD addendum, what has to be in place for automated FDD to work?
[ reveal answer ]
Specific sensors and data have to be available.