WEEK 06 Stage 1 · Concepts 9 hours

Energy, FDD and Re-Tuning

DELIVERABLE Trend-review checklist

Week progress0%
Level 5 badge: Energy + FDD

Learning objectives

  • >Explain the building re-tuning process
  • >Recognize common faults in AHU and plant trends
  • >Explain low delta-T syndrome and its effect on pumping
  • >Describe what fault detection and diagnostics (FDD) needs in order to work

Sessions

Three 2-hour weeknight sessions plus a weekend block. Check each one off as you finish it.

Quiz

Score: 0 / 5 · aim for 4+

Answer in your notebook first, then reveal the answer and grade yourself honestly.

  1. Q1What is building re-tuning?

    [ reveal answer ]
    A low- or no-cost, systematic review of BAS trends and operations to find and fix operational problems.
  2. Q2What would simultaneous heating and cooling look like in AHU trends?

    [ reveal answer ]
    Heating and cooling valves open at the same time, or reheat running while supply air is colder than necessary.
  3. Q3Pumps sit at minimum speed while loop DP stays well above setpoint. What are two likely causes?

    [ reveal answer ]
    An oversized pump or a minimum speed set too high, an open bypass, or very low load.
  4. Q4What is low delta-T syndrome, and how does it affect pumps and chillers?

    [ reveal answer ]
    The return-minus-supply temperature difference runs below design. That forces more flow, raises pumping energy, and keeps chillers from fully loading.
  5. Q5According to the Guideline 36 AFDD addendum, what has to be in place for automated FDD to work?

    [ reveal answer ]
    Specific sensors and data have to be available.