WEEK 01 Stage 1 · Concepts 8 hours
Control Fundamentals
DELIVERABLE DP control-loop sketch, 2-minute owner explanation
Week progress0%
Learning objectives
- >Define setpoint, process variable, error and control output, and identify each in a pump DP loop
- >Distinguish two-position, floating, proportional, PI and PID control and where each is used in HVAC
- >Explain why proportional-only control leaves offset, and what integral action fixes
- >Describe how DDC replaced pneumatic and electric controls, and why hybrid buildings still exist
Sessions
Three 2-hour weeknight sessions plus a weekend block. Check each one off as you finish it.
Quiz
Score: 0 / 5 · aim for 4+
Answer in your notebook first, then reveal the answer and grade yourself honestly.
-
Q1In a variable-speed chilled-water pump DP loop, what is the process variable and what is the controlled output?
[ reveal answer ]
DP is the process variable. Pump speed, through the VFD, is the controlled output. -
Q2Why does proportional-only control leave a steady-state offset?
[ reveal answer ]
The controller needs some error to produce any output, so the loop settles with a residual offset from setpoint. -
Q3What does integral action do, and what is one risk of too much of it?
[ reveal answer ]
It accumulates error over time and drives the offset to zero. Too much causes overshoot, oscillation or windup. -
Q4Name two ways to control a damper actuator other than a modulating 0–10 V signal.
[ reveal answer ]
Two-position (on/off) and floating (tri-state, drive open or drive closed). -
Q5Why is derivative action rarely used in HVAC loops?
[ reveal answer ]
HVAC processes are slow and sensor signals are noisy. Derivative amplifies noise and adds little.
// DONE WHEN
// STRETCH (OPTIONAL)
Building Automation Basics for the HVAC Tech (HVAC School podcast).