WEEK 02 Stage 1 · Concepts 8 hours

Field Devices and VFDs

DELIVERABLE Equipment points list (AI/AO/BI/BO)

Week progress0%
Level 2 badge: Field Devices

Learning objectives

  • >Identify common BAS sensors and their signal types (4–20 mA, 0–10 V, RTD/thermistor, dry contact)
  • >Classify any point as AI, AO, BI, BO or a network point
  • >Explain valve authority and how pressure-independent control valves (PICVs) change system behavior
  • >Compare hardwired and networked VFD integration

Sessions

Three 2-hour weeknight sessions plus a weekend block. Check each one off as you finish it.

Quiz

Score: 0 / 5 · aim for 4+

Answer in your notebook first, then reveal the answer and grade yourself honestly.

  1. Q1Give two advantages of a 4–20 mA signal over 0–10 V on a long wire run.

    [ reveal answer ]
    It isn't affected by voltage drop or much electrical noise. Its live zero (4 mA) also reveals a broken wire.
  2. Q2Classify each point: pump status from a current switch, VFD speed command, DP sensor, pump start/stop.

    [ reveal answer ]
    BI, AO, AI, BO.
  3. Q3What is valve authority, and roughly what value do designers aim for?

    [ reveal answer ]
    The valve's pressure drop divided by the total branch pressure drop. Designers typically aim for about 0.5, and at least 0.25.
  4. Q4How do PICVs affect the choice of DP setpoint for a variable-speed pump?

    [ reveal answer ]
    PICVs hold flow regardless of pressure changes within their range, so the DP setpoint only needs to cover the PICV minimum plus the branch losses. That allows a lower setpoint and makes balancing simpler.
  5. Q5Name two data points a networked VFD provides that a basic hardwired connection does not.

    [ reveal answer ]
    Any two of: kW, kWh, motor current, fault and warning codes, run hours, DC bus voltage.