Field Devices and VFDs
DELIVERABLE Equipment points list (AI/AO/BI/BO)
Learning objectives
- >Identify common BAS sensors and their signal types (4–20 mA, 0–10 V, RTD/thermistor, dry contact)
- >Classify any point as AI, AO, BI, BO or a network point
- >Explain valve authority and how pressure-independent control valves (PICVs) change system behavior
- >Compare hardwired and networked VFD integration
Sessions
Three 2-hour weeknight sessions plus a weekend block. Check each one off as you finish it.
Quiz
Score: 0 / 5 · aim for 4+
Answer in your notebook first, then reveal the answer and grade yourself honestly.
-
Q1Give two advantages of a 4–20 mA signal over 0–10 V on a long wire run.
[ reveal answer ]
It isn't affected by voltage drop or much electrical noise. Its live zero (4 mA) also reveals a broken wire. -
Q2Classify each point: pump status from a current switch, VFD speed command, DP sensor, pump start/stop.
[ reveal answer ]
BI, AO, AI, BO. -
Q3What is valve authority, and roughly what value do designers aim for?
[ reveal answer ]
The valve's pressure drop divided by the total branch pressure drop. Designers typically aim for about 0.5, and at least 0.25. -
Q4How do PICVs affect the choice of DP setpoint for a variable-speed pump?
[ reveal answer ]
PICVs hold flow regardless of pressure changes within their range, so the DP setpoint only needs to cover the PICV minimum plus the branch losses. That allows a lower setpoint and makes balancing simpler. -
Q5Name two data points a networked VFD provides that a basic hardwired connection does not.
[ reveal answer ]
Any two of: kW, kWh, motor current, fault and warning codes, run hours, DC bus voltage.
// DONE WHEN
// STRETCH (OPTIONAL)
The remaining Belimo University modules on sensors and actuators, viewed with a controls mindset.